Central loose tube, single sheathed cable, iRP-increased rodent protected, universal-use, UV.FRLSZH sheath - green, Dca, 01 x 24 fibers OM5 (R859105)

SKU: R859105 Categories: , ,
Environmental Characteristics

Temperature cycling

-35 °C +70 °C / -31 °F +158 °F

Temperature cycling acceptance criteria

Δα ≤ 0,15 dB, reversible

Temperature cycling test method

IEC 60794-1-22:F1

Reversible temperature cycling

-30 °C +70 °C / -22 °F +158 °F

Reversible temperature cycling test method

IEC 60794-1-22:F1

Operation temperature

-30 °C to +70 °C / -22 °F to +158 °F

Thermal load

0.81 MJ/m

Flammability vertical single cable

Pass

Flammability vertical single cable test method

IEC 60332-1-2

Smoke density

Pass

Smoke density test method

EN 61034-1, EN 61034-2

Halogen free, acid gases

Pass

Halogen free, acid gases test method

EN 60754-2

Mechanical Data

In-service tensile strength

800 N

In-service tensile strength acceptance criteria

Δα ≤ 0,05 dB

In-service tensile strength test method

IEC 60794-1-2 E1

Installation tensile strength

2000 N

Installation tensile strength acceptance criteria

Δα ≤ 0,05 dB after test

Installation tensile strength test method

IEC 60794-1-21:E1

Crush resistance long term

1000 N/100mm

Long-term crush resistance acceptance criteria

Δα ≤ 0,05 dB prior release, no damage

Long-term crush resistance test method

IEC 60794-1-21:E3A

Short-term crush resistance

2000 N/100mm

Short-term crush resistance acceptance criteria

Δα ≤ 0,05 dB after release, no damage

Short-term crush resistance test method

IEC 60794-1-21:E3A

Impact resistance

10 Nm, 3 impacts, d=20 mm, R=300 mm

Impact resistance acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Impact resistance test method

IEC 60794-1-21:E4

Torsion

L = 1 m, rotation angle ±180°, 10 cycles

Torsion acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Torsion test method

IEC 60794-1-21:E7

Repeated bending

R=20 x cable diameter, 25 cycles

Repeated bending acceptance criteria

no damage

Repeated bending test method

IEC 60794-1-21:E6

Cable bend

R=40 x cable diameter, 4 turns, 3 cycles

Cable bend acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Cable bend test method

IEC 60794-1-21:E11A

Minimum bend radius in service

110 mm

Minimum bend radius during installation

150 mm

Technical Data

Cable family code

UX1GF

Cable type

Central loose tube cable

Cable version

n.a.

Cable application

universal use

CPR classification

Dca-s2,d1,a1

DoP number

D9031

Fiber type

OM5

Fiber color coding

1.-12.: red, green, blue, yellow, white, grey, brown, violet, turquoise, black, orange, pink13.-24.: red, green, blue, yellow, white, grey, brown, violet, turquoise, natural, orange, pink(ring-marked)

Fiber count per tube

24

Loose tube count

1

Loose tube diameter

3 mm

Armor

Intensified rodent protection

Outer sheath thickness

1,2 mm

Outer sheath material

UV stable FRLSZH

Outer sheath color

green

Cable outer diameter

7,2 mm

Cable weight

58.0 kg/km / 39 lbs/1000ft

DIN / VDE 0888 code

U-DQ(BN)H wbg

CPR classification

Dca

Prod

If you have any questions about the product, please contact us:

 

+1 438 282 7517
info@synge.ca

earthmagnifiercrossmenuchevron-right